Sensocon - Airflow Station

Manufactured by  Sensocon
Follow this Equipment

The Series JFM-S FloSen® Airflow Measuring Stations provide accurate, repeatable measurement of air movement in HVAC ducts

The Series JFM-S FloSen® Airflow Measuring Stations provide accurate, repeatable measurement of air movement in HVAC ducts   
   
The Probes patented ellipticallyshaped sensor design with improved aerodynamic characteristics outperforms more traditional devices, and overcomes loss of accuracy caused by fluid separation at the sensor body. It is designed to maintain a constant parallel airflow pattern over the static sensing ports for more accurate, steady signals under all duct conditions. The elimination of separation results in a stabilized static pressure signal, helping to eliminate “hunting” during fan control.   
   
FloSen® Airflow Probes used in the Sensocon Airflow Measuring Stations utilize a unique in-line groove for total pressure sensing and dual ports for static pressure sensing which produces a higher differential pressure for very low velocity measurements. The total and static pressure measuring points are distributed for equal-area averaging of flows resulting in improved accuracy and reliability. This design permits accurate and stable measurement in highly turbulent flow locations with directional pitch and yaw varying up to 20 degrees without the need for air flow straighteners which restrict airflow and can easily become clogged. The elliptical shape of the FloSen® Airflow Probes allows air to glide unrestricted around the aerodynamically designed sensors and offers the lowest pressure drop of any airflow measuring device available minimizing HVAC operating costs.   
   
The JFM-S Airflow Measuring Stations have been designed for complete installation between ducts. The quantity of FloSen® Airflow Measuring Probes selected for each Flow Station is based on ASHRAE and AMCA standards to produce assured airflow measuring accuracy over a flow turn-down ratio of 17:1.
Active Questions & AnswersAsk a Question

There are no current Discussions

Pump Accessories Service ProvidersView All (3)

Request Support
Features of Airflow Station
  • Flow boundary layers attached to probe surface   
  • No separation effects   
  • No vacuum effects   
  • No vortex generation   
  • Low drag coefficient   
  • High repeatability   
  • Low static pressure signal affected by separation   
  • Vacuum effects limit turndown ratio to 4 to 1   
  • Variable intensity vortices generateddownstream, creates signal amplifications, vibrations and acoustic problems   
  • High drag coefficient creates high pressure loss
  • General Specifications

    There are no General Specifications available.

    Additional Specifications

    Velocity Range:   
    300 – 5000 FPM (1.5 – 25 m/s)   
       
    Probe Length:
       
    8 – 120" (200 – 3000mm)   
       
    Accuracy:   
    +/- 1% F.S.   
       
    Repeatability:   
    +/- 0.1% F.S.   
       
    Temperature Ranges:   
    -40° to 180°F (-40° to 80°C)   
       
    Turn-Down Ratio:   
    17:1   
       
    Pressure Loss:   
    0.004" w.c. @ 700 FPM (1 Pa @ 3.5 m/s)   
       
    Materials (Probe):
       
    Anodized Aluminum or PVC   
       
    Materials (Station):
       
    14 ga Galvanized Steel   
       
    Flow Coefficient:   
    0.785